HAMSTAD is a set of five numerical benchmark cases for checking how building-physics software models heat and moisture transport through building materials. The cases compare calculated responses with analytical solutions or published results from other simulation tools.
Each case examines a different construction or transport process. Together, they help identify which parts of a solver have been evaluated and where further testing is needed.
Examines moisture redistribution through a multilayer wall with interior insulation, including the moisture profile near material interfaces.
Scope of the GenBuildings assessment
The completed work covers four HAMSTAD cases under their documented numerical configurations. Case 3 requires through-material airflow and is outside the evaluated solver scope. The original benchmark programme defines five one-dimensional heat, air and moisture cases. Original publication →
Analytical comparison
Case 2 compares simulated moisture profiles with a Fourier-series solution.
Graphical comparison
Cases 1, 4 and 5 compare responses with published participant figures, subject to the report’s qualifications.
Numerical conservation
Moisture-balance checks assess numerical consistency; they do not establish physical certification.
This case tests how moisture moves between a roof’s load-bearing layer and its interior insulation over five years.
GenBuildings results are compared with published HAMSTAD reference curves. The plots below show the first and fifth years using the same baseline configuration.
Vapour-sealed exterior with changing equivalent temperature; interior at 20°C with prescribed vapour pressure
Rain and solar
No rain or direct solar input; exterior equivalent temperature supplies thermal forcing
First year
First-year moisture response compared with published HAMSTAD results.
Fifth year
Fifth-year moisture response compared with published HAMSTAD results.
The comparison is graphical and remains qualified; it is not a formal pass against numerical acceptance limits.
02
Completed · strong analytical agreement
Isothermal moisture redistribution
Boundary · 45% RHBoundary · 65% RH
Homogeneous material200 mm
Schematic cross-section; not to scale.
Test conditions
Temperature
Constant 20°C
Initial humidity
95% RH
Boundary humidity
45% and 65% RH
Comparison times
100, 300 and 1,000 hours
Results
Moisture profiles against the analytical solution at 100, 300 and 1,000 hours.
Errors against the analytical solution
Time
Maximum point water error
Total water error
100 h
0.008044 kg/m³
0.000538 kg/m²
300 h
0.004051 kg/m³
0.000461 kg/m²
1,000 h
0.001754 kg/m³
0.000362 kg/m²
Assessment: strong analytical agreement under the prescribed isothermal conditions. Small retained vapour permeability and finite surface resistance distinguish the numerical setup from the analytical limit.
03
Not evaluated · outside solver scope
Transport with airflow
This benchmark requires air-pressure-driven transport through porous material, including changes in flow direction. The evaluated solver covers conduction, vapour diffusion and liquid transport, but not the required through-material advective coupling.
Pressure boundaryPressure boundary
Porous materialAirflow through the material ↔
Conceptual transport schematic; this case was not simulated.
Test conditions
Process tested
Heat and moisture transport with pressure-driven airflow
Airflow
Changes in flow direction
GenBuildings status
Not evaluated; required airflow coupling is outside the assessed solver scope
Assessment: not evaluated. Airflow through the material requires additional solver capability.
04
Completed · very good graphical agreement
Coupled heat and rain transients
Exterior · rain exposureInterior
BrickLoad-bearing layer
PlasterFinishing layer
Schematic cross-section; not to scale.
Test conditions
Duration
120 hours
Construction
Brick and plaster
Boundary conditions
Time-varying temperature and vapour-pressure schedules, with rain exposure
Compared outputs
Surface temperature and moisture histories
Moisture response
Surface moisture histories against published participant curves, using the documented timing interpretation.
Wall water at 120 h
18.807879 kg/m²
Integrated moisture residual
2.669 × 10−7 kg/m²
Assessment: very good graphical agreement. The calculation uses a documented boundary-timing interpretation, including a first temperature pulse ending at 79 hours. No formal numerical pass is claimed.
Temperature response
Surface and interface temperatures compared with published HAMSTAD participant results.
05
Completed · very good graphical agreement
Capillary-active interior insulation
Exterior · 0°C / 80% RHInterior · 20°C / 60% RH
Brick365 mm
Mortar15 mm
Insulation40 mm
Schematic cross-section; not to scale.
Test conditions
Duration
60 days
Initial state
25°C and nominal 60% RH
Boundary conditions
Exterior 0°C / 80% RH; interior 20°C / 60% RH
Rain and solar
None
Results at 60 days
Water-content and relative-humidity profiles at 60 days. The visible reference range is not an acceptance band.
Peak water content
63.244 kg/m³
Total wall water at 60 days
2.702001 kg/m²
The peak falls within the approximate published 60–64 kg/m³ graphical range. The RH reference is the digitized HAMSTAD average from van Schijndel et al. (2017), not the HAM-BC 2015 curve.
Assessment: very good graphical agreement. The assessment remains provisional. Digitized curves are not formal acceptance limits; full timestep sensitivity and an energy-budget check remain outstanding.
Conclusion
GenBuildings shows very good graphical agreement for the insulated roof, heat and rain transients, and interior insulation cases, together with strong analytical agreement for isothermal moisture redistribution.
These comparisons demonstrate the evaluated solver’s performance across different heat and moisture transport scenarios. Case 3, which requires airflow through porous materials, remains outside the evaluated scope.